Sign In | Join Free | My tjskl.org.cn
tjskl.org.cn
Products
Search by Category
Home > Relays >

GTH40 UL Magnetic Thermal Overload Relay Electrical Protective Relays

Categories Thermal Overload Relay
Brand Name: KRIPAL
Model Number: UKH-40
Certification: CE, UL
Place of Origin: China
MOQ: 500 pcs
Price: negotiable
Payment Terms: T/T, L/C
Supply Ability: 30000 pcs per month
Delivery Time: 20 days and depends on ordering quantity
Packaging Details: Each unit packed in a individual box
Color: blue/orange
Pins: 3
Type: thermal
Protection: overload
Usage: Usually with ac contactor
Reset: manual / automatic
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

GTH40 UL Magnetic Thermal Overload Relay Electrical Protective Relays


GTH40 UL Magnetic Thermal Overload Relay Electrical Protective Relays


UKH series thermal overload relays apply to circuit of AC 50Hz or 60Hz, rated voltage to below 660V and rated current . 1A-800A for AC motor overload and open-phase protection during long time or intermittent long time service, which can also protect 3-phase serious imbalance and long starting time of motor or long timer operation, can also be used for corresponding AC contactor for electromagnetic starter.

This product has innovative, elegant model and small installation area, functions such as temperature compensation, action indication, automatic and manual reset / stop with steady and reliable performance.

Thermal relay can be combined / connected with contactor or installed separately.

Standard: IEC 60947-1


Applications:


Thermal overload relays are protective devices. They are designed to cut power if the motor draws too much

current for an extended period of time. To accomplish this, thermal overload relays contain a normally closed

(NC) relay. When excessive current flows through the motor circuit, the relay opens due to increased motor

temperature, relay temperature, or sensed overload current, depending on the relay type.


These overload relays are similar to circuit breakers in construction and use, but most circuit breakers differ

in that they interrupt the circuit if overload occurs even for an instant. Thermal overload relays are conversely

designed to measure a motor's heating profile; therefore, overload must occur for an extended period before

the circuit is interrupted.


Specifications:


Type

Thermal component

Rated current (A)

Range of rated current (A)

UKH-40

UKK-40

5

4.0-6.0

6.5

5.0-8.0

7.5

6.0-9.0

8.5

7.0-10.0

11

9.0-13.0

15

12.0-18.0

19

16.0-22.0

22

18.0-26.0

30

24.0-36.0

34

28.0-40.0


Motion Characteristic:


Three-phase Balance Motion Time

No

Times of the setting current

Motion time

Start condition

Ambient temperature

1

1.05

>2h

Cold state

20±5oC

2

1.2

<2h

Heat state(Following the No.1 test)

3

1.5

<4min

4

7.2

10A

2s< Tp≤10s

≤63A

Cold state

10

4s< Tp≤10s

>63A


Phase-losing Motion Characteristic

No

Times of the setting current

Motion time

Start condition

Ambient temperature

Any two phases

Another phase

1

1.0

0.9

>2h

Cold state

20±5oC

2

1.15

0

<2h

Heat state(Following the No.1 test)


Working condition:


1. The installation altitude less than 2000m

2. The surrounding temperature range: from -5°C ~ +40°C

3. In the non-explosive condition. or without adequate erosion and destruction of gas and

dust conductive area .

4. Without rain and snow invade

5. Pollution level 2

Buy GTH40 UL Magnetic Thermal Overload Relay Electrical Protective Relays at wholesale prices
Send your message to this supplier
 
*From:
*To: Zhejiang KRIPAL Electric Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0