Sign In | Join Free | My tjskl.org.cn |
|
Categories | Electromagnetic Flow Meter |
---|---|
Brand Name: | Iflow |
Model Number: | EMF-200-4 |
Certification: | ISO9001, CE, EMC, EXID |
Place of Origin: | China |
MOQ: | 1 |
Price: | negotiable |
Payment Terms: | T/T, L/C, D/P, Western Union |
Supply Ability: | 1000 sets per month |
Delivery Time: | 2-4 weeks |
Packaging Details: | carton / box |
Description: | ElectroMagnetic flow meter |
Tube liner: | PTFE, rubber |
Pressure rating: | 1.6 Mpa |
Temperature: | ±(0.3 + 0.05 * T)K; ΔT = T ± 0.1K |
Electrode: | 316L / Hasteloy-C / Ti / Ta / Pt100 |
Accuracy: | 0.25% , 0.5%, 1% |
Communication: | BACNET/Modbus/RS485/4-20 mA |
Pipe connect: | Flange |
Power supply: | DC, or DC + battery |
Thermal energy meter for building and industrial metering applications, by electromagnetic heat flow meter
Productintroduction
The electromagnetic flow transmitter is a high end thermal energy calculator for industrial applications. Effectively protected against dust and humidity and backlit display. A wide range of built-in functions makes this energy meter a single box solution.
Features
Technical parameters:
1. Diameter: DN15 - DN1200
2. Pressure rating: PN10/PN16/PN25/PN40
3. Media temperature: 0-80 C (Rubber), 0-120 C (PTFE)
4. Environment temperature: 0 - 60 C
5. Protection: IP68 (flow sensor)
6. Explosion proof: EXID
Parameters
Product name | Electromagnetic flowmeter | ||
Product type | Local|compact display | Remote display | Signal converter |
Model | IYF-E | IYF-F | IRT |
Pipe Diameter (mm) | DN10-DN2000 | ||
Power supply | 100-240 VAC / 18-36 VDC | ||
Accuracy | + 0.5% | + 0.5% | + 0.5% |
Power consumption | <6w | <6w | <6w |
Enclosure rating | IP65 | IP68 | IP65 |
Liquid temperature | -25-120℃ | -25-120℃ | -25-120℃ |
Ambient temperature | -25-50℃ | -25-50℃ | -25-50℃ |
Relative humidity | 10-90% | 10-90% | 10-90% |
Meter ratio | 1:100 | 1:100 | 1:100 |
Flow direction | Bi-direction flow | Bi-direction flow | Bi-direction flow |
Communication | RS485 / Bacnet | RS485 / Bacnet | RS485 / Bacnet |
Signal Output | 4-20mA/Pulse/Frequency | 4-20mA/Pulse/Frequency | 4-20mA/Pulse/Frequency |
Measure Accuracy
Pipe Dia (mm) | Velocity (m/s) | Accuracy |
3-20 | <0.3 | + 0.25% FS |
0.3-1 | + 1.0% Readout | |
1-15 | + 0.25% Readout | |
25-600 | 0.1-0.3 | + 0.25% FS |
0.3-1 | + 0.5% Readout | |
1-15 | + 0.3% Readout | |
700-3000 | <0.3 | + 0.25% FS |
0.3-1 | + 1.0% Readout | |
1-15 | + 0.25% Readout |
Applications:
Irrigation, clean water, paper pulp, slurry, sewage, waste water,
HVAC/R system monitoring, residential water meter, industrial &
commercial water utilities
![]() |